Home      Production      Contact Us



RIF-7




REFLECTOMETER RIF-7

DESIGNATION

High-voltage oscillographic reflectometer "RIF-7" (hereinafter "reflectometer ") is designed for distance determination of communication place and electric-power supply cables fault.

The device enables:

  • to detect and determine distance to a place of fault or inhomogeneity by location (reflectometric) method on symmetric and asymmetrical cables;
  • to measure length of cables (including on drums and hanks) or distance to a breakage or short circuit place;
  • to store, save and process results of measurements;
  • as a part of mobile electrical laboratory to determine distance to a cable fault.

In the length to 12 km in all aspects of faults without use of preliminary full burning-through insulation.The device allows to store in the built in non-volatile memory 4 groups of measurements (up to 15 reflectograms in each), and also to store them in the computer for further analysis and the account. (This function is realized under the individual demand of the customer).

Reflectometer is designed for operation in the closed premises (in particular, in caravan cars) under the following conditions:
  • Ambient air temperature range, from -10 °С to +40°С;
  • Air relative humidity at temperature +25°С to 80 %;
  • Atmospheric pressure, mm. Hg -650 - 800;

SPECIFICATIONS
  • maximum measured distance to a fault place, km - 12,3
  • minimum measured distance to a fault place, m - 3
  • discreteness of measurement, m - 0,2
  • parameters of high-voltage outgoing pulses on loading 30 Ohm:
  • amplitude, кV - from 3 to 25
  • duration of front, мкс, no more - 0,15
  • Pulse duration, мкс, not less - 2
  • Parametres of low-voltage outgoing pulses on loading 30 Ohm:
  • Amplitude, In, not less - 5
  • Duration of front, mкsec, no more - 0,02
  • Pulse duration, mкsec, - 0,05-0,5
  • The highest operating voltage of the sensing transducer of pulsing voltage, кV - 60
  • Distance measurement error to a fault place on a high voltage depends on measurement conditions and a breakdown voltage of the damaged section. In case of distance measurement on high voltage in the mode of " floating breakdown ", idling, short circuit the error is from +15 to +25 meters at a distance to 1 km, and from +20 to +40 meters at a distance over 1 km.
  • Weight dimension parameters are given in Section 3 "Composition and complete set of reflectometer ".
  • Reflectometer enables continuous work within 8 hours.
  • Service life of reflectometer - not less than 5 years.
WARRANTY
  • The manufacturer guarantees that RIF-7 complies with requirements of current specifications and norms of User Rules of Operating Electrical Equipment" and “Safety Rules of Operating Electrical Equipment”.
  • Warranty period of operation is 12 months from the date of shipment to the customer.









AID-70/50 SVS-50 SVS-100
UPA-6 UPA-10 UPU_6
IOM-100/16 TANGENS-3М AI-2500 TESTER
UIM-90M UPU-6 AID_70/50
YI-80 GZCH-2500 P-900
RIF-7 SVP-05 SVA-6



All news

Home | Production | Contact Us | Ссылки
AID-70/50 | SVS-50 | SVS-100 | UPA-6 | UPA-10 | UPU_6 | IOM-100/16 | TANGENS-3М | AI-2500 TESTER | UIM-90M | UPU-6 | AID_70/50 | YI-80 | GZCH-2500 | P-900 | RIF-7 | SVP-05 | SVA-6

site tree contact us add to fvorite